HEFA 5T Air Handler
  • Cooling Output Tons: 5 tons
    • Based on 44°F (6°C) supply fluid and 95°F (35°) ambient air
    • 900 CFM air flow and 12 GPM fluid flow
  • Heating Output BTU: 91,731 Btu/h
    • Based on 180°F (82°C) supply fluid and 32°F (0°C) ambient air
  • Blower:
    • Backward inclined
  • Motor: 0.6 HP, variable speed
  • Electrical: 120V, single phase, 60 Hz, 15 A
  • Controls:  Thermostatic and fan speed
  • Weight: 130 lbs (59 kg)
  • Dimensions: 29″ l x 18.5″ w x 28.5″ h
  • Circulation: Single supply and return
    • 3/4″ quick couplers (standard)
  • Condensate pump: 3/4″ drain hose connection

HEFA 5T Air Handler

Features

  • Versatile air handler that is ideal for year-round climate control applications such as cooling, heating, and drying.
  • The ultra-compact and mobile design allows the air handler to be used where required, even where space is limited.
  • The fan operates on a 120 Volt 15 amp circuit, allowing the air handler to be used anywhere there is electricity.
  • The compact size and low power requirements allow the air handler to meet the needs of remote locations.
  • High-volume air flow ensures there is even air temperature throughout the structure.
  • User-friendly thermostatic and speed controls to maintain desired conditions and maximize efficiency. An optional humidistat available if required.
  • Integrated condensate pump for automatic collection and removal of condensate from the environment.

Cooling

  • Connect several air handlers to a chiller to achieve your cooling needs.
  • The air handler is designed with an oversize coil to maximize efficiency. Cooling targets are achieved with less water and airflow per ton of cooling.
  • The oversize coil is only three cores thick, which minimizes the air pressure drop across the coil to maximize fan output.

Heating

  • When winter comes, the hydronic air handler delivers clean, low-humidity air. With a DryAir hydronic heating system, energy costs are minimized as warm inside air is re-heated, rather than heating cold outside air, like other systems.

Drying

  • When drying, the low humidity environment produced by the air handler saves time and money for contractors with jobs such as: interior drywall, paint and coatings.