- Heat Source: Low-pressure steam
- Input: 1,000,000 Btu/h
- Heat Area: 40,000 ft²
- Thaw Area: 18,000 ft²
- Cure Area: 48,000 ft²
- Weight: 405 lbs
- Dimensions: 47″ l x 28″ w x 75″ h
HESF 1000 Central Heating Unit
– PATENT PENDING –
Steam-to-fluid plate heat exchanger utilizing steam as the heat source
Features
- The system transfers heat from “on-site” steam to a circuit of heat-transfer-fluid that enables the use of any of the DryAir accessories for heat distribution.
- Automatic temperature control allows the user to set the desired supply-fluid temperature. Temperature is maintained by modulating the flow of steam through the exchanger.
- One unit will provide enough heating capacity to heat up to 50,000 square feet! (dependent on the steam source capacity)
- Using an existing steam source could prove to be the most versatile and economical approach to delivering temporary heat on a construction site / building renovation.
Specifications
- Steam Requirements
- For use with low pressure steam (15 psi or less)
- Steam supply and condensate return pipe connections to unit are 1½” FNPT
- Condensate trap is an integral part of the unit
- Must be connected to the site supply by a licensed steam-fitter/pipe-fitter
- Steam pressure reducing valves not included
- Fluid Distribution
- 2nd circuit – heat transfer fluid circuit
- 2″ hose and Kamlock connections
- Reservoir On-board “open-vented” glycol reservoir
- External connection for an optional external extended reservoir
- A selector valve is used to select either the on-board reservoir or the external reservoir
- Pump
- 2HP, 28SFLA, 13FLA
- 50 – 75 US GPM
- Electrical
- System requirements – 230V, 1 Ph, 60Hz, 30A
- Control circuitry – 24V
- Heat Exchanger
- Copper-brazed stainless steel plates
- Heat exchange **1000 kBtu/h
**with 1,036 lb/h of steam and 50 US GPM of fluid flow
- Optional
- Extended Reservoir package – Cart type